Clim'Up MUSE Outdoor Unit, 4.1 - 12 kW
MUSE outdoor units are equipped with a ROTARY DC INVERTER compressor, a 4-way valve for reversing heating/cooling mode, and a modulating fan.
They are designed to be combined with 1,2,3,4 or 5 indoor units (UME, UCE, UGE or UCARE) (the relevant specifications are qvqilqble to download and in the table of recommendations below).
MUSE |
40-2 |
50-2 |
60-3 |
80-3 |
100-4 |
120-5 |
||
|
Output in cooling mode (min./max.) |
kW |
4.1 (1.8-4.51) |
5.3 (2.0-5.83) |
6.2 (2.2-6.71) |
7.9 (2.3-8.69) |
10.5 (2.5-11.00) |
12.00 (2.77-12.7) |
|
Output in heating mode (min./max.) |
kW |
4.8 (2.05-5.28) |
5.6 (2.21-6.16) |
6.6 (2.39-7.26) |
8.2 (2.45-9.02) |
11.00 (2.67-11.20) |
13.00 (2.96-12.80) |
|
Output in cooling mode |
BTU/hr |
14000 |
18000 |
21200 |
27000 |
35800 |
41000 |
|
Output in heating mode |
BTU/hr |
16400 |
19100 |
22500 |
28000 |
37500 |
44400 |
|
Electrical power consumption in cooling mode at nominal output |
kW |
1.24 |
1.75 |
1.92 |
2.46 |
3.92 |
4.32 |
|
Electrical power consumption in heating mode at nominal output |
kW |
1.15 |
1.54 |
1.78 |
2.27 |
3.04 |
3.75 |
|
Max. air flow (outdoor unit) |
m3/h |
2300 |
2300 |
3100 |
3100 |
4000 |
4200 |
|
SEER |
|
6.2 |
7.1 |
6.5 |
6.3 |
6.1 |
6.1 |
|
|
A++ |
A++ |
A++ |
A++ |
A++ |
A++ |
|
|
SCOP |
|
4.1 |
4.1 |
4.4 |
4.0 |
4.0 |
4.0 |
|
|
A+ |
A+ |
A+ |
A+ |
A+ |
A+ |
|
|
Acoustic pressure of outdoor unit |
dB[A] |
54 |
55 |
56 |
58 |
61 |
61 |
|
Acoustic power of outdoor unit |
dB[A] |
61 |
62 |
65 |
65 |
68 |
68 |
|
Outdoor unit weight |
kg |
34 |
36 |
44 |
46 |
74 |
75 |
|
Refrigerant connections (Fluid - Gas) |
pouces |
1/4" - 3/8" |
1/4" - 3/8" |
1/4" - 3/8" |
1/4" - 3/8" |
1/4" - 3/8" |
1/4" - 3/8" |
|
Total max. length between indoor and outdoor units |
m |
40 |
40 |
60 |
60 |
80 |
80 |
|
Max. length between indoor and outdoor units |
m |
25 |
25 |
30 |
30 |
35 |
35 |
|
Max. height difference between indoor and outdoor units |
m |
15 |
15 |
15 |
15 |
15 |
15 |
|
Max. height difference between all indoor and outdoor units |
m |
10 |
10 |
10 |
10 |
10 |
10 |
|
Preloaded length |
m |
15 |
15 |
22.5 |
22.5 |
30 |
37.5 |
|
Additional load of F32 refrigerant per additional meter |
g / m |
20 |
20 |
20 |
20 |
20 |
20 |
|
Nominal charge of R32 refrigerant fluid |
kg |
0.92 |
0.95 |
1.1 |
1.05 |
2.3 |
2.3 |
|
Voltage/Frequency values |
V / Hz |
220-240 / 50 |
220-240 / 50 |
220-240 / 50 |
220-240 / 50 |
220-240 / 50 |
220-240 / 50 |
|
Nominal current in cooling mode |
A |
5.4 |
7.6 |
8.3 |
10.7 |
18.7 |
20.6 |
|
Maximum current |
A |
10 |
11 |
13 |
16 |
22.5 |
24.5 |
|
Power cable cross-section |
mm2 |
3G1.5 |
3G1.5 |
3G1.5 |
3G2.5 |
3G4.0 |
3G4.0 |
|
Circuit breaker |
|
C16A |
C16A |
C16A |
C20A |
C25A |
C25A |
|
Cross-section of cable connecting the indoor and outdoor units |
mm2 |
4G1.5 |
4G1.5 |
4G1.5 |
4G2.5 |
4G2.5 |
4G2.5 |